Appendix 1 Error Codes
Appendix 1.8 List of error codes (6000 to 6999)
6106
[TRK. TRANS. ERR.]
A timeout error occurred in tracking (data
transmission). (This error may be caused by
tracking cable removal or other system power-
off (including reset).)
The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common information: Tracking transmission
data classification
Individual information: -
Diagnostic timing
Always
Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
Confirm the redundant system startup
procedure, and execute a startup again.
RUN: On
ERR.:On
CPU Status:Continue
QnPRH
6107
[TRK. TRANS. ERR.]
A data sum value error occurred in tracking (data
reception). (This can be detected from the control
system or standby system of the redundant
system.)
Collateral information
Common information: -
Individual information: -
Diagnostic timing
Always
Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
Confirm the redundant system startup
procedure, and execute a startup again.
RUN: On
ERR.:On
CPU Status:Continue
QnPRH
6108
[TRK. TRANS. ERR.]
A data error (other than sum value error)
occurred in tracking (data reception). (This error
may be caused by tracking cable removal or
other system power-off (including reset).)
The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common information: -
Individual information: -
Diagnostic timing
Always
Check the CPU module or tracking cable. If
the same error occurs, the cause is a
failure of the CPU module or tracking cable.
Please consult your local Mitsubishi
representative.
Confirm the redundant system startup
procedure, and execute a startup again.
RUN: On
ERR.:On
CPU Status:Continue
QnPRH
6110
[TRK. SIZE ERROR]
The tracking capacity exceeded the allowed
range. (This can be detected from the control
system or standby system of the redundant
system.)
Collateral information
Common information: Reason(s) for tracking
size excess error
Individual information: -
Diagnostic timing
When an END instruction executed
Reexamine the tracking capacity.
RUN: On
ERR.:On
CPU Status:Continue
QnPRH
6111
[TRK. SIZE ERROR]
The control system does not have enough file
register capacity for the file registers specified in
the tracking settings. (This can be detected from
the control system or standby system of the
redundant system.)
Collateral information
Common information: -
Individual information: -
Diagnostic timing
When an END instruction executed
Switch to the file registers of which capacity is
greater than the file registers specified in the
tracking settings.
RUN: On
ERR.:On
CPU Status:Continue
QnPRH
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU