EasyManua.ls Logo

Mitsubishi Electric Q13UDVCPU - Page 405

Mitsubishi Electric Q13UDVCPU
720 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
403
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.9 List of error codes (7000 to 10000)
7004
[MULTI CPU DOWN]
In a multiple CPU system, a data error occurred in
communication between the CPU modules.
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
Always
Check the system configuration to see if
modules are mounted in excess of the
number of I/O points.
If there is no problem in the system
configuration, the cause is a hardware
failure of the CPU module. Please consult
your local Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
QnU
7010
[MULTI EXE. ERROR]
In a multiple CPU system, a faulty CPU module
was mounted.
In a multiple CPU system, a CPU module
incompatible with the multiple CPU system was
mounted. (The CPU module compatible with the
multiple CPU system was used to detect an
error.)
In a multiple CPU system, any of the CPU No. 2
to 4 was reset with power ON. (The CPU whose
reset state was cancelled was used to detect an
error.)
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Read the common information of the error
using the programming tool and replace the
faulty CPU module.
Replace the CPU module with the one
compatible with the multiple CPU system.
Do not reset any of the No. 2 to 4 CPU
modules.
Reset CPU No. 1 and restart the multiple
CPU system.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00/Q01
Qn(H)
QnPH
QnU
[MULTI EXE. ERROR]
In a multiple CPU system, the version of the
software package (PPC-DRV-01)
*2
for the PC
CPU module is 1.06 or earlier.
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Change the software package (PPC-DRV-
01)
*2
for the PC CPU module to the version
1.07 or later.
Q00/Q01
[MULTI EXE. ERROR]
The Q172(H)CPU(N) or Q173(H)CPU(N) is
mounted on the multiple CPU high-speed main
base unit (Q3DB). (This may result in a module
failure.)
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Replace the Q172(H)CPU(N) and
Q173(H)CPU(N) with the Motion CPU
compatible with the multiple CPU high-speed
main base unit.
Qn(H)
QnPH
[MULTI EXE. ERROR]
The Universal model QCPU (except Q02UCPU)
and Q172(H)CPU(N) are mounted on the same
base unit. (This may result in a module failure.)
Collateral information
Common information: Module No. (CPU No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Check the QCPU and Motion CPU that can
be used in a multiple CPU system, and
change the system configuration.
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents

Related product manuals