EasyManua.ls Logo

Mitsubishi Electric Q13UDVCPU - Page 422

Mitsubishi Electric Q13UDVCPU
720 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
420
4184
H
Ethernet I/F
Error
Communication processing buffer has run out
of space due to consecutive reception of
request messages using the MC protocol.
Communication processing buffer has run out
of space because received data read is not
performed or cannot keep up with the volume.
Communication processing is disabled due to
insufficient space in the communication
processing buffer.
For MC protocol, send a request after receiving
a response to the previous request.
For socket communication, enable received data
read.
For socket communication, decrease the
number of data sent from the target device.
QnU
*2
LCPU
*2
4185
H
Ethernet I/F
Error
Connection to the target device is
disconnected before sending a response using
the MC protocol.
Connection to the target device is
disconnected during communication.
For MC protocol, keep the connection until a
response is sent.
Keep the connection until a sequence of
communication is completed.
Other error such as 4184
H
may be the cause. If
any other error has occurred, take corrective
action of that error.
QnU
*2
LCPU
*2
4186
H
Ethernet I/F
Error
System error (The argument data in OS is
abnormal.)
Check that the power supply module and the
CPU module are mounted/connected properly.
Check that the system is operating within the
general specifications of the CPU module.
Check whether the power capacity is sufficient.
Reset the CPU module.
Execute again. If the same error code is
displayed, the cause is a hardware failure of the
CPU module. Please consult your local
Mitsubishi representative.
QnU
*2
LCPU
*2
4187
H
Ethernet I/F
Error
System error (The wait processing in OS is
abnormal.)
Check that the power supply module and the
CPU module are mounted/connected properly.
Check that the system is operating within the
general specifications of the CPU module.
Check whether the power capacity is sufficient.
Reset the CPU module.
Execute again. If the same error code is
displayed, the cause is a hardware failure of the
CPU module. Please consult your local
Mitsubishi representative.
QnU
*2
LCPU
*2
4188
H
Ethernet I/F
Error
System error (The data length in OS is
abnormal.)
Check that the power supply module and the
CPU module are mounted/connected properly.
Check that the system is operating within the
general specifications of the CPU module.
Check whether the power capacity is sufficient.
Reset the CPU module.
Execute again. If the same error code is
displayed, the cause is a hardware failure of the
CPU module. Please consult your local
Mitsubishi representative.
QnU
*2
LCPU
*2
4189
H
Ethernet I/F
Error
System error (The protocol information in OS is
abnormal.)
Check that the power supply module and the
CPU module are mounted/connected properly.
Check that the system is operating within the
general specifications of the CPU module.
Check whether the power capacity is sufficient.
Reset the CPU module.
Execute again. If the same error code is
displayed, the cause is a hardware failure of the
CPU module. Please consult your local
Mitsubishi representative.
QnU
*2
LCPU
*2
418A
H
Ethernet I/F
Error
System error (The address data of
communicating module in OS is abnormal.)
Check that the power supply module and the
CPU module are mounted/connected properly.
Check that the system is operating within the
general specifications of the CPU module.
Check whether the power capacity is sufficient.
Reset the CPU module.
Execute again. If the same error code is
displayed, the cause is a hardware failure of the
CPU module. Please consult your local
Mitsubishi representative.
QnU
*2
LCPU
*2
Error code
(Hexadecimal)
Error item Error details Corrective action
Corresponding
CPU

Table of Contents

Related product manuals