455
APPENDICES
A
Appendix 2 List of Special Relay Areas
(1) Diagnostic information
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU
SM0 Diagnostic errors
OFF: No error
ON: Error
• This relay turns on if an error is
detected by diagnostics. (Also turns on
if an error is detected by an
annunciator or the CHK instruction.)
• This relay remains on even after the
system returns to normal.
S (Error) New
Qn(H)
QnPH
QnPRH
• This relay turns on if an error is
detected by diagnostics. (Also turns on
if an error is detected by an
annunciator.)
• This relay remains on even after the
system returns to normal.
Q00J/Q00/Q01
QnU
LCPU
SM1
Self-diagnostic
error
OFF: No error
ON: Error
• This relay turns on if an error is
detected by self-diagnostics. (Remains
off if an error is detected by an
annunciator or the CHK instruction.)
• This relay remains on even after the
system returns to normal.
S (Error)
M9008
Qn(H)
QnPH
QnPRH
• This relay turns on if an error is
detected by self-diagnostics. (Remains
off if an error is detected by an
annunciator.)
• This relay remains on even after the
system returns to normal.
New
Q00J/Q00/Q01
QnU
LCPU
SM5
Error common
information
OFF: No error common
information
ON: Error common
information
This relay turns on if error common
information data exists when SM0 turns
on.
S (Error) New
QCPU
LCPU
SM16
Error individual
information
OFF: No error
individual
information
ON: Error individual
information
This relay turns on if error individual
information data exists when SM0 turns
on.
S (Error) New
QCPU
LCPU
SM50 Error reset OFF ON:Error clear Conducts error reset operation U New
QCPU
LCPU
SM51 Battery low latch
OFF: Normal
ON: Battery low
• This relay turns on if the battery voltage
of the CPU module or the memory card
drops below the rated value.
• This relay remains on even after the
battery voltage returns to normal.
• The on/off timing is synchronized with
that of the BAT. LED.
S (Error)
M9007
Qn(H)
QnPH
QnPRH
QnU (except
QnUDV)
• This relay turns on if the battery voltage
of the CPU module drops below the
rated value.
• This relay remains on even after the
battery voltage returns to normal.
• The on/off timing is synchronized with
that of the BAT. LED.
New
QnUDV
LC
PU
• This relay turns on if the battery voltage
of the CPU module drops below the
rated value.
• This relay remains on even after the
battery voltage returns to normal.
• The on/off timing is synchronized with
that of the ERR. LED.
New Q00J/Q00/Q01
SM52 Battery low
OFF: Normal
ON: Battery low
This relay has the same specifications as
those of SM51 except that this relay turns
off after the battery voltage returns to
normal.
S (Error) M9006
QCPU
LCPU