Appendix 2 List of Special Relay Areas
(1) Diagnostic information
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU
SM0 Diagnostic errors
OFF: No error
ON: Error
This relay turns on if an error is
detected by diagnostics. (Also turns on
if an error is detected by an
annunciator or the CHK instruction.)
This relay remains on even after the
system returns to normal.
S (Error) New
Qn(H)
QnPH
QnPRH
This relay turns on if an error is
detected by diagnostics. (Also turns on
if an error is detected by an
annunciator.)
This relay remains on even after the
system returns to normal.
Q00J/Q00/Q01
QnU
LCPU
SM1
Self-diagnostic
error
OFF: No error
ON: Error
This relay turns on if an error is
detected by self-diagnostics. (Remains
off if an error is detected by an
annunciator or the CHK instruction.)
This relay remains on even after the
system returns to normal.
S (Error)
M9008
Qn(H)
QnPH
QnPRH
This relay turns on if an error is
detected by self-diagnostics. (Remains
off if an error is detected by an
annunciator.)
This relay remains on even after the
system returns to normal.
New
Q00J/Q00/Q01
QnU
LCPU
SM5
Error common
information
OFF: No error common
information
ON: Error common
information
This relay turns on if error common
information data exists when SM0 turns
on.
S (Error) New
QCPU
LCPU
SM16
Error individual
information
OFF: No error
individual
information
ON: Error individual
information
This relay turns on if error individual
information data exists when SM0 turns
on.
S (Error) New
QCPU
LCPU
SM50 Error reset OFF ON:Error clear Conducts error reset operation U New
QCPU
LCPU
SM51 Battery low latch
OFF: Normal
ON: Battery low
This relay turns on if the battery voltage
of the CPU module or the memory card
drops below the rated value.
This relay remains on even after the
battery voltage returns to normal.
The on/off timing is synchronized with
that of the BAT. LED.
S (Error)
M9007
Qn(H)
QnPH
QnPRH
QnU (except
QnUDV)
This relay turns on if the battery voltage
of the CPU module drops below the
rated value.
This relay remains on even after the
battery voltage returns to normal.
The on/off timing is synchronized with
that of the BAT. LED.
New
QnUDV
LC
PU
This relay turns on if the battery voltage
of the CPU module drops below the
rated value.
This relay remains on even after the
battery voltage returns to normal.
The on/off timing is synchronized with
that of the ERR. LED.
New Q00J/Q00/Q01
SM52 Battery low
OFF: Normal
ON: Battery low
This relay has the same specifications as
those of SM51 except that this relay turns
off after the battery voltage returns to
normal.
S (Error) M9006
QCPU
LCPU