EasyManua.ls Logo

Mitsubishi Electric Q13UDVCPU - Page 468

Mitsubishi Electric Q13UDVCPU
720 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
466
SM410 0.1 second clock
This relay repeatedly turns on and off
at the specified interval.
This relay starts with off at power-on or
reset of the CPU module. (Note if the
specified time has elapsed, on/off
status will change even during program
execution.)
S (Status
change)
M9030
QCPU
LCPU
SM411 0.2 second clock M9031
SM412 1 second clock
This relay repeatedly turns on and off
at the specified interval.
This relay starts with off at power-on or
reset of the CPU module. (Note if the
specified time has elapsed, on/off
status will change even during program
execution.)
S (Status
change)
M9032
QCPU
LCPU
SM413 2 second clock M9033
SM414 2n second clock
This relay repeatedly turns on and off
at the interval specified in SD414 (unit:
second). (If the value of SD414 is
changed, the time that has passed
after the previous ON/OFF interval of
SM414 is counted as the next interval,
and the ON/OFF status is changed at
the next interval that is newly
specified.)
Example: When the value of SD414 is
changed from 3 to 10.
This relay starts with off at power-on or
reset of the CPU module. (Note if the
specified time has elapsed, on/off
status will change even during program
execution.)
S (Status
change)
M9034 format
change
QCPU
LCPU
SM415 2n (ms) clock
This relay repeatedly turns on and off
at the interval specified in SD415 (unit:
ms). (If the value of SD415 is changed,
the time that has passed after the
previous ON/OFF interval of SM415 is
counted as the next interval, and the
ON/OFF status is changed at the next
interval that is newly specified. SM415
operates in the same way as SM414.)
This relay starts with off at power-on or
reset of the CPU module. (Note if the
specified time has elapsed, on/off
status will change even during program
execution.)
S (Status
change)
New
Qn(H)
QnPH
QnPRH
QnU
LCPU
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU
0.05s
0.05s
0.1s
0.1s
0.5s
0.5s
1s
1s
ns
ns
SM414
OFF
3
seconds
3
seconds
The time that has passed after
the previous ON/OFF interval
of SM414 is counted as the
next interval.
10
seconds
10
seconds
ON
SD414 3 10
Change of the value
n ms
n ms

Table of Contents