466
SM410 0.1 second clock
• This relay repeatedly turns on and off
at the specified interval.
• This relay starts with off at power-on or
reset of the CPU module. (Note if the
specified time has elapsed, on/off
status will change even during program
execution.)
S (Status
change)
M9030
QCPU
LCPU
SM411 0.2 second clock M9031
SM412 1 second clock
• This relay repeatedly turns on and off
at the specified interval.
• This relay starts with off at power-on or
reset of the CPU module. (Note if the
specified time has elapsed, on/off
status will change even during program
execution.)
S (Status
change)
M9032
QCPU
LCPU
SM413 2 second clock M9033
SM414 2n second clock
• This relay repeatedly turns on and off
at the interval specified in SD414 (unit:
second). (If the value of SD414 is
changed, the time that has passed
after the previous ON/OFF interval of
SM414 is counted as the next interval,
and the ON/OFF status is changed at
the next interval that is newly
specified.)
Example: When the value of SD414 is
changed from 3 to 10.
• This relay starts with off at power-on or
reset of the CPU module. (Note if the
specified time has elapsed, on/off
status will change even during program
execution.)
S (Status
change)
M9034 format
change
QCPU
LCPU
SM415 2n (ms) clock
• This relay repeatedly turns on and off
at the interval specified in SD415 (unit:
ms). (If the value of SD415 is changed,
the time that has passed after the
previous ON/OFF interval of SM415 is
counted as the next interval, and the
ON/OFF status is changed at the next
interval that is newly specified. SM415
operates in the same way as SM414.)
• This relay starts with off at power-on or
reset of the CPU module. (Note if the
specified time has elapsed, on/off
status will change even during program
execution.)
S (Status
change)
New
Qn(H)
QnPH
QnPRH
QnU
LCPU
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU
0.1s
0.1s
1s
1s
SM414
OFF
3
seconds
3
seconds
The time that has passed after
the previous ON/OFF interval
of SM414 is counted as the
next interval.
10
seconds
10
seconds
ON
SD414 3 10
Change of the value
n ms
n ms