45
CHAPTER 2 SYSTEM CONFIGURATION
2
2.3 Precautions for System Configuration
(7) Precautions when using AnS/A series modules
*1 Only multidrop link function can be used. The computer link function and printer function cannot be used.
1) When using the AnS series special function modules shown below, a limitation is placed on an accessible
device range.
A1SJ71J92-S3 type JEMANET interface module
A1SD51S type intelligent communication module
Device Accessible device range
Input (X), Output (Y) X/Y0 to 7FF
Internal relay (M), Latch relay (L) M/L0 to 8191
Link relay (B) B0 to FFF
Timer (T) T0 to 2047
Counter (C) C0 to 1023
Data register (D) D0 to 6143
Link register (W) W0 to FFF
Annunciator (F) F0 to 2047
2) The modules listed below cannot be used.
Product Model
MELSECNET/10 network module
A1SJ71LP21, A1SJ71BR11, A1SJ71LR21, A1SJ71QLP21,
A1SJ71QLP21S, A1SJ71QBR11, A1SJ71QLR21
MELSECNET(II), /B data link module A1SJ71AP21, A1SJ71AR21, A1SJ71AT21B
Ethernet module
A1SJ71E71N-T, A1SJ71E71N3-T, A1SJ71E71N-B2(-B5),
A1SJ71QE71N-T, A1SJ71QE71N3-T, A1SJ71QE71N-B2(-B5)
Serial communication module, computer link module
A1SJ71UC24-R2(-PRF), A1SJ71QC24(-R2), A1SJ71QC24N(-R2),
A1SJ71QC24N1(-R2)
Computer link/multidrop link module
A1SJ71UC24-R4
*1
CC-Link system master/local module A1SJ61BT11, A1SJ61QBT11
ME-NET interface module A1SJ71ME81
3) The AnS/A series dedicated instructions for the following modules cannot be used.
Rewriting using the FROM or TO instruction is required.
Product Model
High speed counter module A1SD61, A1SD62, A1SD62D(-S1), A1SD62E
MELSECNET/MINI-S3 A1SJ71PT32-S3, A1SJ71T32-S3
Positioning module A1SD75P1-S3(P2-S3/P3-S3)
ID module A1SJ71ID1-R4, A1SJ71ID2-R4