582
(20)Redundant system (other system CPU information
*1
)
The special register (SD1600 to SD1650) is valid when the redundant system is in backup mode and is invalid in
separate mode. The special register (SD1651 to SD1690) is valid when the redundant system is in backup mode
or in separate mode. All bits in SD1600 to SD1690 are set to "0" for stand-alone systems.
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
host CPU
SD
*2
Corresponding
CPU
SD1600
System error
information
System error
information
When an error is detected by the redundant system error
check, the bit corresponding to the error turns on. The bit
turns off when the error is cleared.
If any of b0, b1, b2 and b15 is on, the other bits are off.
In the debug mode, b0, b1, b2 and b15 are all off.
S (Every
END
processing)
QnPRH
SD1601
System
switching
results
System
switching
results
Reason(s) for system switching is stored.
When a system is switched, the reason for system switching
is stored in SD1601 of both systems.
This register is initialized with zero (0) stored when the
system is powered on from off or is reset.
The following shows the values stored in this register.
0: Initial value (control system has never been switched)
1: Power-off, reset, H/W failure, or watchdog timer error
*1
2: Stop error (except for watchdog timer error)
3: A system switching request from network module
16: Control system switching instruction
17: System switching request from a programming tool
*1 When the system is switched upon the power-off or
reset of the control system, "1" is not stored in SD1601
of the new standby system.
S (when
system is
switched)
QnPRH
SD1602
System
switching
dedicated
instruction
parameter
System
switching
dedicated
instruction
parameter
When a system is switched by the SP.CONTSW instruction,
the argument of the instruction is stored. (The argument is
stored in SD1602 of both systems at the system switching.)
SD1602 is only valid when "16" is stored in SD1601.
SD1602 is updated only when a system is switched by the
control system switching instruction.
S (when
system is
switched)
QnPRH
SD1610
Other
system
diagnostic
error
Diagnostic
error code
The code of the error occurred in the other system is stored.
The value in SD0 of the CPU module on the other system is
reflected.
S (Every
END
processing)
SD0 QnPRH
SD1611
to
SD1613
Other
system
diagnostic
error
occurrence
time
Diagnostic
error
occurrence
time
The date and time of the diagnostics error occurred in the
other system are stored.
Data format is the same as SD1 to SD3.
The values in SD1 to SD03 of the CPU module on the other
system are reflected.
S (Every
END
processing)
SD1 to SD3 QnPRH
b1 b0b15 b2
Fixed to 0
SD1600
Each bit
0: OFF
1: ON
Tracking cable is not
connected or damaged
Power-OFF, reset,
watchdog timer error or
hardware failure occurred
in other system
Other system stop error
(except watchdog timer
error)
Bit turns on when failing to
connect with other system.
The following causes are
shown below:
Tracking H/W failure
Host system WDT error
Cannot recognize other
system therefore causing
error