2 - 38 
2   SYSTEM CONFIGURATION 
 
POINTS 
 
(Note-1) : Overcurrent protection 
The overcurrent protection device shuts off the 5VDC or 24VDC circuit 
and stops the system if the current flowing in the circuit exceeds the 
specified value. When this device is activated, the power supply module 
LED is switched OFF or dimly lit. If this happens, eliminate the cause of 
the overcurrent and start up the system again. 
 
(Note-2) : Overvoltage protection 
The overvoltage protection device shuts off the 5VDC circuit and stops 
the system if a voltage of 5.5 to 6.5V is applied to the circuit. When this 
device is activated, the power supply module LED is switched OFF. If 
this happens, switch the input power OFF, then ON to restart the system. 
The power supply module must be changed if the system is not booted 
and the LED remains OFF.  
 
(Note-3) : Permissible instantaneous power off time 
Permissible instantaneous power off is selected to use the power supply 
module.