Error code
Remote control:
7-segment display:
LED Green Red
Indoor
Outdoor
Content
'14 • KX-SM-221
WAIT
WAIT
(1)
Keeps ashing
Stays OFF
Keeps ashing Keeps ashing
1. Applicable model
5. Troubleshooting
All models
(In case that is kept
on displaying on the remote
control for more than 2 minutes
after power ON.)
Diagnosis Countermeasure
NO
NO
NO
NO
NO
NO
NO
YES
NO
NO
YES
YES
YES
YES
YES
YES
YES
is kept on
displaying on the remote
control for more than 2
minutes after power ON.
Once turn OFF the breaker
and turn ON it again at 3
minutes after power OFF.
Isn't
the power fuse (5A) on the
outdoor control PCB
blown?
Is
the connection of wire
between noise filter and
inverter PCBs OK?
Are
the wires between indoor
and outdoor units
connected properly ?
Is
AC220-240V detected
between L-N at indoor
terminal block?
Is
AC380-415V detected
between L1-L2, L2-L3, L3-L1
respectively at outdoor
terminal block?
Does
indoor green LED keep
flashing?
Does
indoor green LED flash
2 times?
Is
AC380-415V detected at
the secondary side of
noise filter PCB terminal?
Does it become normal?
Replace fuse
Refer next page.
WAIT
Replace noise lter PCB.
Connect wires correctly.
Indoor control PCB anomaly
Replace it.
Indoor/outdoor control PCB
anomaly
Replace it.
Remote control anomaly
Replace it.
Breakage of wires for remote
control
Replace it.
Correct the connecting wires
between indoor and outdoor
units.
Outdoor control PCB anomaly
Replace it.
Breakage of connecting wire
Noise.
Indoor control PCB anomaly
Replace it.
2. Error detection method
3
.
Condition of error displayed
4. Presumable cause
Fuse blown
Noise filter anomaly
Anomalous connection of
wire between PCBs
Indoor control PCB anomaly
Remote control anomaly
Breakage of connecting wires
of remote control
Outdoor control PCB anomaly
Note:
(1)
When anomaly occurs during establishing communication between indoor and outdoor unit, error code E5 is displayed (outdoor red
LED
ash 2-times).
In case of E5, the way of troubleshooting is same as above mentioned (except for checking of connecting wire).
When reset the power after E5 occurs, if this anomaly recurs, is displayed on remote control. If power ON/OFF is repeated in
a short period (within 1 minute), may be displayed. In such case, please wait for 3 minute after the power breaker OFF.
(2)
If any error is detected 30 minutes after displaying “ ” on the remote control, the display changes to “INSPECT I/U”.
WAIT
WAIT
WAIT
WAIT
-
71
-

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDC224KXZPE1 and is the answer not in the manual?

Mitsubishi Heavy Industries FDC224KXZPE1 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDC224KXZPE1
CategoryAir Conditioner
LanguageEnglish

Related product manuals