Countermeasures against deterioration of the 400 V class motor insulation
PRECAUTIONS FOR USE OF THE INVERTER
87
3
3.5 Countermeasures against deterioration of
the 400 V class motor insulation
In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals. Especially in a
400 V class motor, the surge voltage may deteriorate the insulation. When the 400 V class motor is driven by the inverter,
consider the following countermeasures:
Countermeasures for induction motors
It is recommended to take one of the following countermeasures:
Rectifying the motor insulation and limiting the PWM carrier frequency according
to the wiring length
For the 400 V class motor, use an insulation-enhanced motor.
Specifically,
Order a "400 V class inverter-driven insulation-enhanced motor".
For the dedicated motor such as the constant-torque motor and low-vibration motor, use an "inverter-driven dedicated
motor".
•Set Pr.72 PWM frequency selection as indicated below according to the wiring length.
Suppressing the surge voltage on the inverter side
For the FR-A846-01800(55K) or lower, connect the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) to the
output side.
For the FR-A846-02160(75K) or higher, connect the sine wave filter (MT-BSL/BSC) to the output side.
Countermeasures for PM motors
When the wiring length exceeds 50 m, set "9" (6 kHz) or less in Pr.72 PWM frequency selection.
NOTE
For the details of Pr.72 PWM frequency selection, refer to the FR-A800 Instruction Manual (Detailed).
For the details of the surge voltage suppression filter (FR-ASF-H/FR-BMF-H), refer to the Instruction Manual of each option.
A surge voltage suppression filter (FR-ASF-H/FR-BMF-H) can be used under V/F control and Advanced magnetic flux vector
control.
A sine wave filter (MT-BSL/BSC) can be used under V/F control. Do not use the filters under different control modes.
The carrier frequency is limited during PM sensorless vector control. (Refer to the FR-A800 Instruction Manual (Detailed).)
Wiring length
50 m or shorter 50 m to 100 m Longer than 100 m
Pr.72 PWM frequency selection 15 (14.5 kHz) or lower 9 (9 kHz) or lower 4 (4 kHz) or lower