PARAMETERS
148
Pr. 52 "Control panel/PU main
display data selection"
Related parameter
4.2.42 Actual operation hour meter clear (Pr. 171)
Pr. 171 "actual operation hour meter
clear"
You can clear the monitor (actual operation hour) value which is selected when Pr. 52
is "23".
Parameter
Number
Factory
Setting
Setting
Range
171 0 0
<Setting>
Write "0" in the parameter to clear the actual operation hour.
Pr. 173 to Pr. 176
'
''
'
Refer to Pr. 160.
4.2.43 Input terminal function selection (Pr. 180 to Pr. 183)
Pr. 180 "RL terminal function selection"
Pr. 181 "RM terminal function selection"
Pr. 182 "RH terminal function selection"
Pr. 183 "MRS terminal function selection"
Use these parameters to select/change the input terminal functions.
Parameter
Number
Terminal
Symbol
Factory
Setting
Factory-Set Terminal
Function
Setting
Range
180 RL 0
Low-speed operation
command (RL)
0 to 8, 16, 18
181 RM 1
Middle-speed operation
command (RM)
0 to 8, 16, 18
182 RH 2
High-speed operation
command (RH)
0 to 8, 16, 18
183 MRS 6 Output shut-off (MRS) 0 to 8, 16, 18