4.1 Parameter List
PARAMETERS
63
4 PARAMETERS
4.1 Parameter List
4.1.1 Parameter list
Func-
tion
Param-
eter
Number
Name
Setting
Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Custo-
mer
Setting
0 Torque boost (Note 1) 0 to 30% 0.1%
6%/4%
(Note 11)
72
1 Maximum frequency 0 to 120Hz
0.01Hz (Note 3)
120Hz 73
2 Minimum frequency 0 to 120Hz
0.01Hz (Note 3)
0Hz 73
3 Base frequency (Note 1) 0 to 400Hz
0.01Hz (Note 3)
60Hz 74
4
Multi-speed setting
(high speed)
0 to 400Hz
0.01Hz (Note 3)
60Hz 75
5
Multi-speed setting
(middle speed)
0 to 400Hz
0.01Hz (Note 3)
30Hz 75
6
Multi-speed setting
(low speed)
0 to 400Hz
0.01Hz (Note 3)
10Hz 75
7 Acceleration time
0 to 3600 s/
0 to 360 s
0.1 s/0.01 s
5 s/10s
(Note 4)
76
8 Deceleration time
0 to 3600 s/
0 to 360 s
0.1 s/0.01 s
5 s/10s
(Note 4)
76
Basic functions
9
Electronic thermal O/L
relay
0 to 500A 0.01A
Rated
output
current
(Note 5)
78
10
DC injection brake
operation frequency
0 to 120Hz
0.01Hz
(Note 3)
3Hz 79
11
DC injection brake
operation time
0 to 10 s 0.1 s 0.5 s 79
12 DC injection brake voltage 0 to 30% 0.1% 6% 79
13 Starting frequency 0 to 60Hz 0.01Hz 0.5Hz 80
14
Load pattern selection
(Note 1)
0 to 3 1 0 81
15 Jog frequency 0 to 400Hz
0.01Hz
(Note 3)
5Hz 82
16
Jog acceleration/
deceleration time
0 to 3600 s/
0 to 360 s
0.1 s/0.01 s 0.5 s 82
18
High-speed maximum
frequency
120 to
400Hz
0.1Hz
(Note 3)
120Hz 73
19
Base frequency voltage
(Note 1)
0 to 1000V,
8888,9999
0.1V 9999 74
20
Acceleration/deceleration
reference frequency
1 to 400Hz
0.01Hz
(Note 3)
60Hz 76
21
Acceleration/deceleration
time increments
0, 1 1 0 76
22
Stall prevention operation
level
0 to 200% 0.1% 150% 83
23
Stall prevention operation
level compensation factor
at double speed (Note 6)
0 to 200%,
9999
0.1% 9999 83
24
Multi-speed setting
(speed 4)
0 to 400Hz,
9999
0.01Hz
(Note 3)
9999 75
25
Multi-speed setting
(speed 5)
0 to 400Hz,
9999
0.01Hz
(Note 3)
9999 75
26
Multi-speed setting
(speed 6)
0 to 400Hz,
9999
0.01Hz
(Note 3)
9999 75
Standard operation functions
27
Multi-speed setting
(speed 7)
0 to 400Hz,
9999
0.01Hz
(Note 3)
9999 75
Parameter List

Table of Contents