PARAMETERS
97
Pr. 1 "maximum frequency"
Pr. 7 "acceleration time"
Pr. 8 "deceleration time"
Pr. 18 "high-speed maximum
frequency"
Pr. 44 "second acceleration/
deceleration time"
Pr. 45
"second deceleration time"
Related parameters
4.2.23 Remote setting function selection (Pr. 59)
Pr. 59 "remote setting function selection"
If the operator panel is located away from the
control box, you can use contact signals to
perform continuous variable-speed operation,
without using analog signals.
!
By merely setting this parameter, you can use
the acceleration, deceleration and setting clear
functions of the motorized speed setter (FR-FK).
!
When the remote function is used, the output frequency of the inverter can be
compensated for as follows:
External operation mode Frequency set by RH/RM operation plus built-in
frequency setting potentiometer or external analog
frequency command
PU operation mode Frequency set by RH/RM operation plus PU's digitally-set
frequency
Parameter
Number
Factory
Setting
Setting
Range
59 0 0, 1, 2
Deceleration (RM)
Clear (RL)
Acceleration (RH)
Forward rotation (STF)
ON
ON
Power supply
ON
0Hz
(Note)
ON
ON
ON
ON
ON
ON
When Pr.59=1
When Pr.59=
2
ON
ON
Output
frequency(Hz)
Note: External operation frequency or PU operation frequency other than multi-speed
Operation
Pr. 59
Setting
Remote setting function
Frequency setting storage function
(E
2
PROM)
0No

1Yes Yes
2Yes No
!
Use Pr. 59 to select whether the remote setting function is used or not and whether
the frequency setting storage function* in the remote setting mode is used or not.
When "remote setting function - yes" is selected, the functions of signals RH, RM
and RL are changed to acceleration (RH), deceleration (RM) and clear (RL). Use
Pr. 180 to Pr. 183 (input terminal function selection) to set signals RH, RM and RL.
* Frequency setting storage function
The remote setting frequency (frequency set by RH, RM operation) is stored into
memory. When power is switched off once, then on again, operation is resumed at
this setting of the output frequency. (Pr. 59=1)
<Frequency setting storage condition>
Frequency at the time when the start signal (STF or STR) has switched off
Frequency at the time when the RH (acceleration) and RM (deceleration) signals
have remained off for more than 1 minute