164
Errors (Alarms)
(4) Write errors
Operation Panel Indication
Er1 FR-PU04 Control Mode
Name
Write disable error
Description
Write was performed with "1" (write disable) set in Pr. 77
"parameter write disable selection".
Frequency jump setting range overlapped.
Parameter write was performed though the operation panel does
not have the write precedence.
Corrective action
Check the setting of Pr. 77 "parameter write disable selection".
(Refer to page 108.)
Check the settings of Pr. 31 to 36 (frequency jump). (Refer to
page 80.)
When the FR-PU04 is fitted and n17 = "0" or "1", the operation of
the operation panel is invalid.
For RS-485 connector (RS-485) communication, the operation of
the operation panel is invalid.
Operation Panel Indication
Er2 FR-PU04
In PU/EXT Mode
OPERATOR ERR
Name
Write-while-running error/mode designation error
Description
Write was performed during operation.
An attempt was made to change the Pr. 79 setting to the
operation mode where the operation command has been input.
Write was performed in the external operation mode.
Corrective action
After stopping operation, make parameter setting.
After setting the operation mode to the "PU operation mode",
make parameter setting. (Refer to page 109.)
Operation Panel Indication
Er3 FR-PU04 Incr I/P
Name
Calibration error
Description
Analog input bias and gain calibration values are too close.
Corrective action
Check the settings of C3, C4, C6 and C7 (calibration functions).
(Refer to page 82.)