EasyManua.ls Logo

Mitsubishi FR - S500 - 2.2 List of parameters classified by purpose of use

Mitsubishi FR - S500
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
Function (Parameter) list
2
FUNCTIONS
Parameter List
Output terminal functions
41
Up-to-
frequency
sensitivity
0 to 100% 1% 10% 86
42
Output
frequency
detection
0 to 120Hz 0.1Hz 6Hz 87
43
Output
frequency
detection for
reverse
rotation
0 to 120Hz, - - - 0.1Hz - - - 87
Second functions
44
Second
acceleration/
deceleration
time
0 to 999s 0.1s 5s 67
45
Second
deceleration
time
0 to 999s, - - - 0.1s - - - 67
46
Second
torque boost
0 to 15%, - - - 0.1% - - - 63
47
Second V/F
(base
frequency)
0 to 120Hz, - - - 0.1Hz - - - 65
Current detection
48
Output current
detection level
0 to 200% 1% 150% 88
49
Output current
detection
period
0 to 10s 0.1s 0s 88
50
Zero current
detection
level
0 to 200% 1% 5% 89
51
Zero current
detection
period
0.05 to 1s 0.01s 0.5s 89
Func-
tion
Para-
meter
Indica-
tion
Name Setting Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Cus-
tomer
Setting

Table of Contents

Related product manuals