10
Comfort setting heating
Default Heating curve setting
The basic heating is set using menu 2.1.2 and with the “Heating
curve offset” knob.
If the room temperature does not reach the target, readjustment
may be necessary.
If you do not know the correct settings, use the basic data from
the automatic heating control system diagram on the right.
Offset heating curve
Heating curve
2 . 1 . 2
9
Menu 2.1.2 Heating curve
Heating curve offset for system 2 can be made in menu 3.1
NOTE
Wait one day between settings so as to stabilise the
temperatures.
Setting with diagrams
The diagram shows the relation between the outdoor temperature
in the area and the target supply water temperature of the heating
system. This is set under menu 2.1.2, “Heating curve”. Limitations,
which are not in the diagrams, can be set in the control system’s
permitted min and max temperatures. (See menu 2.1.4 and 2.3 as
well as 3.3 and 3.4)
Heating curve offset -2
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
- 40 C
UTETEMPERATUR
- 10
0
10
- 5
+ 5
30
40
50
60
70
C
FRAMLEDNINGSTEMPERATUR
- 20 - 30
FÖRSKJUTNING
VÄRMEKURVA (-2)
VÄRMEKURVA
HEATING CURVE
OFFSET HEAT CURVE
Outdoor temperature
Supply temperature
30
40
50
60
70
C
FRAMLEDNINGSTEMPERATUR
- 40 C
UTETEMPERATUR
- 10
0
10
- 20 - 30
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
V
ÄRMEKURVA
- 5
+ 5
FÖRSKJUTNING
VÄRMEKURVA (0)
Outdoor temperature
Supply temperature
1514 13 12 11 10
8
7
6
5
4
3
2
1
- 40 C
UTETEMPERATUR
- 10
0
10
- 5
+ 5
30
40
50
60
70
C
FRAMLEDNINGSTEMPERATUR
- 20 - 30
FÖRSKJUTNING
VÄRMEKURVA (+2)
9
VÄRMEKURVA
Outdoor temperature
Supply temperature
Heating curve offset 0
Heating curve offset +2
HEATING CURVE
HEATING CURVE
OFFSET HEAT CURVE