29
Control
7.0 [N] Clock
Menu 7.1 [N] Date
The current date is set here.
Menu 7.2 [N] Time
Here the current time is set.
Menu 7.3.0 [U] Temp set back
Settings, e.g. for night reduction can be selected in the
submenus to this menu.
Menu 7.3.1 [U] Set back time
The time for the set back operation, e.g. night reduction is
chosen here.
Menu 7.3.2 [U] Set back temp +/-
Changes of the heat curve during set back operation period, e.g.
the night reduction is set here.
Setting range: -10 – 10
Default value: 0
Menu 7.3.3 [U] Heating system
The heating system to apply the set back operation is selected
here. If heating system 2 is present the menu can be set to
“Off ”, “System 1”, “System 2” or “System 1+2”. In other
cases only “Off” and “System 1” can be selected.
Setting range: Off, System 1, System 2, System 1+2
Menu 7.3.4 [U] Return
Return to menu 7.3.0.
Menu 7.4.0 [U] Extra hot water
Settings are made in the sub-menus of this menu when extra
hot water is required on a specic day.
Menu 7.4.1 – 7.4.7 [U] XHW Monday – XHW Sunday
Here you select the period for respective days when extra hot
water should be activated. Hours and minutes for both start and
stop are shown. Equal values mean that extra hot water is not
activated. Time can be set past midnight.
Setting range: 00:00 – 23:45
Menu 7.4.8 [U] Return
Return to menu 7.4.0.
Menu 7.5.0 [U] Vacation set back
Holiday settings are made in the sub-menus to this menu.
When the holiday function is active, the calculated supply line
temperature is reduced according to the setting and hot water
charging can be switched off.
When the holiday function is deactivated, the heat pump
operates hot water for an hour, before periodic extra hot water
is activated (even if periodic extra hot water is activated in
menu 1.7).
Note!
The holiday setting does not deactivate cooling.
Menu 7.5.1 [U] Vacation begins
The start date for holiday changing is set here. The date is
changed by pressing the enter button. The holiday change starts
applying at 00:00 on the selected date.
Same date in menu 7.5.1 and 7.5.2 deactivates the holiday
function.
Menu 7.5.2 [U] Vacation ends
The end date for holiday changing is set here. The date is
changed by pressing the enter button. The holiday change stops
applying at 23:59 on the selected date.
Same date in menu 7.5.1 and 7.5.2 deactivates the holiday
function.
Menu 7.5.3 [U] Heating system
The heating system to apply the vacation set back is selected
here. If heating system 2 is present the menu can be set to “Off ”,
“System 1”, “System 2” or “System 1+2”. In other cases only
“Off” and “System 1” can be selected.
Setting range: Off, System 1, System 2, System 1+2
Menu 7.5.4 [U] Offset heating curve
How much the heating curve is to be offset during the holiday
period is set here.
If the relevant heating system has a room sensor, the change is
given in degrees.
Setting range: -10 – 10
Menu 7.5.5 [U] HW off
You can choose if hot water operation is cancelled during the
holiday period
Setting range: No, Yes
Menu 7.5.6 [U] Return
Return to menu 7.5.0.
Menu 7.6 [N] Return
Return to menu 7.0.