M
Marcus YoderAug 25, 2025
Why am I getting an overflow error on my Mitsubishi Controller?
- SsmcconnellAug 25, 2025
An overflow error in your Mitsubishi Controller can occur if: 1) When a linear counter is in use, an add pulse is input beyond the current value of 2147483647. 2) When a linear counter is in use, a subtract pulse is input below the current value of -2147483647. To resolve this, preset the controller to clear the overflow error.