SW2 setting
Display detail
Explanation for display Unit
:
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 secs. 0.5secs. 2 secs.
Subcool on error occurring SC
0~130
Cooling = TH6-TH3
Heating = TH5-TH2
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 secs. 0.5secs. 2 secs.
Thermo-on time until error stops
0~999
0~999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 secs. 0.5secs. 2 secs.
Indoor pipe temperature/Liquid
(TH2 (3))
Indoor 3
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
Indoor pipe temperature/Cond./Eva. (TH5
(3))
Indoor 3
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When there is no indoor unit, “00” is displayed.
50
1
:
1
ON
23456
Discharge superheat on error occurring
SHd
0~255
Cooling = TH4-TH6
Heating = TH4-TH5
1
ON
23456
1
ON
23456
1
ON
23456
1
ON
23456
:
Minute
:
15
1
15
4
1
ON
23456
Normal
Overvoltage error
Undervoltage error
Input current sensor error
L
1-phase open error
Abnormal power synchronous signal
Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
Power circuit board
Power circuit board
Controller circuit board
Power circuit board
Description Detection point Display
00
01
02
04
08
U9 Error status during the Error
postponement period
Code
display