EasyManua.ls Logo

Mitsubishi PUHZ-P250YHA3R3 - MAINTENANCE AND DISASSEMBLY; 11-6. HOW TO CHECK THE PARTS

Mitsubishi PUHZ-P250YHA3R3
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
47
1
2
3
4
5
6
M
Gray
Orange
Red
Yellow
Black
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10~30)
Thermistor (TH3)
<Outdoor pipe>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<Outdoor 2-phase pipe>
Thermistor (TH7)
<Outdoor>
Normal
160k~410k
4.3k~9.6k
TH4
TH3
TH6
TH7
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
)
Solenoid valve coil
<Four-way valve>
(21S4)
Motor for compressor
(MC)
Linear expansion valve
(LEV-A)
Normal
Abnormal
Open or short
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20)
Normal
Gray - Black Gray - Red
Gray - Yellow
Gray - Orange
Abnormal
46 ± 3
Open or short
Refer to next page.
Fan motor (MF1,MF2)
0.30
Measure the resistance between the terminals with a tester.
(Winding temperature 20
)
Normal Abnormal
Open or short
W
V
U
1435 ± 150
11-6. HOW TO CHECK THE PARTS
PUHZ-P200YHA PUHZ-P250YHA PUHZ-P200YHA3 PUHZ-P250YHA3
PUHZ-P200YHA3R1 PUHZ-P250YHA3R1 PUHZ-P200YHA3R2 PUHZ-P250YHA3R2
PUHZ-P200YHA3R3 PUHZ-P250YHA3R3

Related product manuals