64
SW2 setting
1
ON
23456
Display detail
Explanation for display
Unit
Capacity setting display
Displayed as an outdoor capacity code.
Code
display
1
ON
23456
1
ON
23456
Outdoor unit setting information
Indoor pipe temperature/Liquid (TH2(1))
Indoor 1
– 39~88
Code
display
:
– 39~88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
1
ON
23456
1
ON
23456
Indoor room temperature (TH1)
8~39
Capacity
P200
P250
Code
40
50
Setting details
•
The tens digit (Total display for applied setting)
• The ones digit
H·P /
Cooling only
Single phase / 3 phase
Display details
0 : H·P 1 : Cooling only
0 :
Single phase
2 : 3 phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : For high humidity
(Example) When heat pump, 3 phase and defrosting
(normal) are set up, “20” is displayed.
1
ON
23456
1
ON
23456
Indoor pipe temperature/Cond./Eva.
(TH5(1))
Indoor 1
– 39~88
– 39~88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
:
– 39~88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
:
:
:
8~39
Indoor pipe temperature/Liquid (TH2(2))
Indoor 2
– 39~88
Indoor pipe temperature/Cond./Eva.
(TH5(2))
Indoor 2
– 39~88
1
ON
23456
The number of connected indoor units
Unit
0~4
(The number of connected indoor units are dis-
played.)