8
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar)
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
PUHZ-P200YHA
PUHZ-P250YHA
PUHZ-P200YHA3(R1/R2/R3)
PUHZ-P250YHA3(R1/R2/R3)
COOLING
MODE
HEATING
59
SPL(dB)
59
LINE
6
DATA
6-1. REFILLING REFRIGERANT CHARGE (R410A : kg)
6-2. COMPRESSOR TECHNICAL DATA
Piping length (one way)
10m
20m
30m
40m
50m
Factory
charged
4.8
5.9
5.3
6.5
5.8
7.1
6.7
8.3
7.6
9.5
60m
8.5
10.7
70m
9.4
11.9
5.8
7.1
Service Ref.
PUHZ-P200YHA
PUHZ-P200YHA3
PUHZ-P200YHA3R1
PUHZ-P200YHA3R2
PUHZ-P200YHA3R3
PUHZ-P250YHA
PUHZ-P250YHA3
PUHZ-P250YHA3R1
PUHZ-P250YHA3R2
PUHZ-P250YHA3R3
U-V
U-W
W-V
Unit
Compressor model
Winding
Resistance
( )
(at 20°C)
ANB52FFJMT
ANB52FFPMT
0.30
0.30
0.30
PUHZ-P200, 250YHA
PUHZ-P200, 250YHA3
PUHZ-P200, 250YHA3R1
PUHZ-P200, 250YHA3R2
PUHZ-P200, 250YHA3R3
ANB52FFPMT
0.30
0.30
0.30
For pipe longer than 30 m,
additional charge is required.
6-3. NOISE CRITERION CURVES
1.5m
1m
MICROPHONE
UNIT
GROUND