43
5.Ifdisplayedaddressorattributeis
FRESHMASTER,
Indoorunitdetectsabnormalitywhen
indoorunittransmittedtoFRESH
MASTERandtherewasnoreply(ACK).
1Duringsequentialoperation
ofindoorunitandFRESH
MASTERofotherrefrigerant
system,ifindoorunittransmits
toFRESHMASTERwhile
outdoorunitpowersupplyof
samerefrigerantsystemwith
FRESHMASTERisturnedoff
orwithin2minutesofrestart,
abnormalityisdetected.
2Contactfailureoftransmission
wireofindoorunitorFRESH
MASTER
3Disconnectionoftransmission
connector(CN2M)ofindoor
unitorFRESHMASTER
4Defectivetransmittingreceiving
circuitofindoorunitorFRESH
MASTER
Check code Abnormal point and detection method
Case
Judgment and action
A7
(6607)
6.Ifdisplayedaddressorattributeis
LOSSNAY,
Indoorunitdetectsabnormalitywhen
indoorunittransmittedtoLOSSNAYand
therewasnoreply(ACK).
1Ifthepowersupplyof
LOSSNAYisturnedoff,indoor
unitdetectsabnormalitywhen
ittransmitstoLOSSNAY.
2Duringsequentialoperation
ofindoorunitandLOSSNAY
ofotherrefrigerantsystem,
ifindoorunittransmitsto
LOSSNAYwhileoutdoorunit
powersupplyofsamerefrig-
erantsystemwithLOSSNAY
isturnedofforwithin2min-
utesofrestart,abnormalityis
detected.
3Contactfailureoftransmis-
sionwireofindoorunitof
LOSSNAY
4Disconnectionoftransmission
connector(CN2M)ofindoor
unit
5Defectivetransmittingreceiv-
ingcircuitofindoorunitor
LOSSNAY
7.Ifdisplayedaddressorattributeisnon-
existent,
1Theunitofformeraddress
doesnotexistasaddress
switchhaschangedwhilethe
unitwasenergized.
2Abnormalityisdetected
whenindoorunittransmit-
tedbecausetheaddress
ofFRESHMASTERand
LOSSNAYarechangedafter
sequentialoperationofFRESH
MASTERandLOSSNAYby
remotecontroller.
Fromthepreviouspage.
4.Ifdisplayedaddressorattributeis
remotecontroller,
Indoorunitdetectsabnormalitywhen
indoorunittransmittedtoremotecontrol-
lerandtherewasnoreply(ACK).
1Duringgroupoperationwith
indoorunitofmulti-refrigerant
system,ifindoorunittransmit
toremotecontrollerwhileout-
doorunitpowersupplyofone
refrigerantsystemisturnedoff
orwithin2minutesofrestart,
abnormalityisdetected.
2Contactfailureoftransmission
wireofremotecontrolleror
indoorunit
3
Disconnectionoftransmission
connector(CN2M)ofindoorunit
4Defectivetransmittingreceiving
circuitofindoorunitorremote
controller
Same as mentioned in “A7” of the previous
page.