EasyManua.ls Logo

Mitsubishi PUZ-A18NHA6 - Power Circuit Board Check

Mitsubishi PUZ-A18NHA6
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59
10-6-5. Check method of power circuit board
Normal
Is the voltage of main incoming power
198–253 V AC
198–253 V AC
198–253 V AC
Check the breaker and power supply.
Is the voltage to the compressor
(U-V,U-W and V-W) balanced?
Note: To check the voltage of the parts on this board with a tester is difficult due to its location.
Test points are limited.
Check wiring.
Check model setting switch SW6
on the outdoor controller circuit board.
Replace the power circuit board.
Is the voltage of CNDC(PNK) on outdoor
controller circuit board 280–350V DC?
Check wiring.
Check power circuit board.
Check noise filter circuit board.
Yes
Yes
Yes
No
No
No
Power circuit board check
7
6
5
4
3
2
1
Noise
Filter
Circuit
Board
Power circuit board
Conv.
Circuit
CNDC
(PNK)
7 6 5 4 3 2 1
Comp
U
V
W
U-V 10250 V AC
V-W 10250 V AC
W-U 10250 V AC
LI NI
L N
TB1
290–350 V DC
Circuit diagram
3
1
PUZ-A18/24NHA6 PUZ-A18/24NHA6-BS
PUY-A12/18/24NHA6 PUY-A12/18/24NHA6-BS
OCH577A