85
SW2setting
1
ON
2 3 4 5 6
Displaydetail
Explanationfordisplay
Unit
Capacitysettingdisplay
Displayedasanoutdoorcapacitycode
Code
display
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Outdoorunitsettinginformation
Indoorpipetemperature/Liquid(TH2(1))
Indoor1
−38to190
Code
display
˚F
[:]
−38to190[−39to88:]
(Whenthetemperatureis0ºForless,“–”and
temperaturearedisplayedbyturns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoorroomtemperature(TH1)
46to102
Capacity
A12N
A18N
A24N
A30N
A36N
A42N
Code
9
10
11
Capacity Code
14
20
25
Setting details
• The tens digit (Total display for applied setting)
• The ones digit
H·P /
Cooling only
Single phase / 3 phase
Display details
0 : H·P 1 : Cooling only
0 :
Single phase
2 :
3 phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : For high humidity
(Example)Whenheatpump,3phaseand
defrosting(normal)aresetup,“20”is
displayed.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoorpipetemperature/Cond./Eva.
(TH5(1))
Indoor1
−38to190
−38to190[−39to88:]
(Whenthetemperatureis0˚Forless,“–”and
temperaturearedisplayedbyturns.)
˚F
[:]
−38to190[−39to88:]
(Whenthetemperatureis0˚Forless,“–”and
temperaturearedisplayedbyturns.)
−38to190[−39to88:]
(Whenthetemperatureis0˚Forless,“–”and
temperaturearedisplayedbyturns.)
˚F
[:]
˚F
[:]
˚F
[:]
46to102[8to39:]
Indoorpipetemperature/Liquid(TH2(2))
Indoor2
−38to190
Indoorpipetemperature/Cond./Eva.
(TH5(2))
Indoor2
−38to190
1
ON
2 3 4 5 6
Thenumberofconnectedindoorunits
Unit
0to3
(Thenumberofconnectedindoorunitsaredis-
played.)
Theblacksquare()indicatesaswitchposition.
OCH577A