87
SW2setting
Displaydetail
Explanationfordisplay Unit
1
ON
2 3 4 5 6
%
Capacitysave
0to100
Whenairconditionerisconnectedto
M-NETandcapacitysavemodeis
demanded,avaluefrom“0”to”100”is
displayed.
Whenthereisnosetting
ofcapacitysave,“100”is
displayed.
0to100
(Whenthecapacityis100%,hundredsdigit,tens
digitandonesdigitaredisplayedbyturns.)
(Example)When100%;
0.5s0.5s2s
Code
display
Errorpostponementcodehistory(2)
ofoutdoorunit
Postponementcodedisplay
Blinking:Duringpostponement
Lighting:Cancellationofpostponement
“00”isdisplayedincaseofnopostponement.
Code
display
Errorpostponementcodehistory(3)
ofoutdoorunit
Postponementcodedisplay
Blinking:Duringpostponement
Lighting:Cancellationofpostponement
“00”isdisplayedincaseofnopostponement.
Code
display
Checkcodehistory(3)(Oldest)
Alternatedisplayofabnormalunit
numberandcode.
Whennoerrorhistory,“0”and“––“aredisplayedby
turns.
3:Outdoorpipetemperature/Liquid(TH3)
6:Outdoorpipetemperature/2-phase(TH6)
7:Outdoorambienttemperature(TH7)
8:Outdoorheatsink(TH8)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Errorthermistordisplay
Whenthereisnoerrorthermistor,
“–“isdisplayed.
Code
display
Operationfrequencyonerroroccurring
0to255
0to255
(Whenitis100Hzormore,hundredsdigit,tensdigit
andonesdigitaredisplayedbyturns.)
(Example)When125Hz;
0.5s0.5s2s
1
ON
2 3 4 5 6
Hz
Fansteponerroroccurring
0to10
0to10
1
ON
2 3 4 5 6
Step
00
1
25
1
Theblacksquare(■)indicatesaswitchposition.