4 - 13 4 - 13
4 SFC PROGRAM CONFIGURATION
MELSEC-Q
(3) An operation HOLD step (with transition check) becomes inactive when any of the following
occur:
(a) When the end step of the corresponding block is executed. (Except when SM327 is ON)
(b) When an SFC control instruction (rBLm) designates a forced END at the block in question.
(c) When an SFC control instruction (rBLm\Sn, rSn) designates a reset at the block in question.
(d) When a reset occurs at the device designated as the SFC information register's block
START/END device.
(e) When a reset step for resetting the step in question becomes active.
(f) When "S999" is designated at the reset step in the same block.
(g) When the SFC START/STOP command (SM321) is switched OFF.
(4) Block STOP processing
Make a block STOP using the STOP/RESTART bit of the SFC information devices or the
block STOP instruction of the SFC control instructions.
The processing of the active step in the block where a block STOP was made is as described
below.
(a) When the "block STOP-time operation output flag (SM325)" is OFF (coil output OFF)
The step becomes inactive when the processing of the corresponding block is performed
first after a block STOP request.
• All coil outputs turn OFF.
• However, the coils turned ON by the SET instruction remain ON.
(b) When the "block STOP-time operation output flag (SM325)" is ON (coil output held)
The coil outputs remain ON during a block STOP and after a block RESTART.

Table of Contents

Other manuals for Mitsubishi Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q Series and is the answer not in the manual?

Mitsubishi Q Series Specifications

General IconGeneral
I/O PointsUp to 4096 points
CommunicationEthernet, RS-232, RS-485
I/O ModulesDigital, Analog, Specialized
Programming LanguageFunction Block Diagram, Structured Text
Power Supply24V DC, 100-240V AC
Operating Temperature0°C to 55°C
Shock Resistance147 m/s2 acceleration, 3 times in each of X, Y, and Z directions
Program CapacityUp to 252K steps

Related product manuals