4 SETUP AND PROCEDURES BEFORE OPERATION
4.4 Wiring
The wiring precautions and examples of module connection are provided below.
4.4.1 Wiring precautions
In order to optimize the functions of the A/D converter module and ensure system
reliability, external wiring that is protected from noise is required.
Please observe the following precautions for external wiring:
(1) Use separate cables for the AC control circuit and the external input signals of the
Q64AD/Q68ADV(I) to avoid the influence of the AC side surges and inductions.
(2) Do not mount the cables close to or bundle them with the main circuit line, a high-
voltage cable or a load cable from other than the PLC. This may increase the
effects of noise, surges and induction.
(3) Perform an one-point grounding for shielded lines and the shields of sealed
cables.
(4) A solderless terminal with insulating sleeve cannot be used for the terminal block.
Covering the cable-connection portion of the solderless terminal with a marked
tube or an insulation tube is recommended.

Table of Contents

Other manuals for Mitsubishi Q64AD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q64AD and is the answer not in the manual?

Mitsubishi Q64AD Specifications

General IconGeneral
BrandMitsubishi
ModelQ64AD
CategoryMedia Converter
LanguageEnglish

Related product manuals