EasyManua.ls Logo

Mitsubishi SRK35ZS-S

Mitsubishi SRK35ZS-S
335 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-
238
-
'16 • SCM-T-199
None
Excessive noise/vibration (3/3)
Outdoor
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Adjustment
during commissioning
Does noise/vibration occur when the
cooling/heating operation is in
anomalous condition?
From previous page
YES
If insufcient cooling/
heating problem happens
due to anomalous operating
conditions at cooling/
heating, followings are
suspicious.
Overcharge of refrigerant
Insufficient charge of
refrigerant
Intrusion of air, nitrogen,
etc.
In such occasion, it is
necessary to recover
refrigerant, vacuum-dry
and recharge refrigerant.
* Since there could be
many causes of noise/
vibration, the above do not
cover all.
In such case, check the
conditions when, where,
how the noise/vibration
occurs according to
following check point.
Indoor/outdoor unit
• Cooling/heating/fan
mode
• Startup/stop/during
operation
Operating condition
(Indoor/outdoor
temperatures, pressure)
Time it occurred
Operation data retained
by the remote control
such as compressor
rotation speed, heat
exchanger temperature,
EEV opening degree, etc.
Tone (If available, record
the noise)
Any other anomalies
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
Note:
Error code
Remote control:
LED Green Red
Indoor
Content

Table of Contents

Other manuals for Mitsubishi SRK35ZS-S

Related product manuals