253
-
'16 • SCM-T-199
E10
Excessive number of connected
indoor units (more than 17 units)
by controlling with one remoto control
Keeps ashing
Stays OFF
Outdoor
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Aren't more than 17
indoor units connected to one
remote control?
NO
YES
Defective remote control
Replace.
Reduce to 16 or less units.
2. Error detection method
When it detects more than 17 of
indoor units connected to one
remote contorl
3 .
Condition of error displayed
Same as above
4. Presumable cause
Excessive number of indoor
units connected
Defective remote control
Note:
Error code
Remote control:
LED Green Red