243
-
'16 • SCM-T-199
INSPECT I/U
INSPECT I/U
(Connection of 3 units or more remote control)
Keeps ashing
Stays OFF
Outdoor
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Reduce to 2 units or less.
Change remote control
setting to “Master”. (SW1
on remote control PCB)
Change address. (SW2 on
indoor control PCB)
Change to master. (SW5-1,
2 on indoor control PCB)
Correct
Correct
Defective outdoor sub PCB
Replace.
Broken connecting wire
Correct.
Defective indoor control or
power PCB
Replace.
2. Error detection method
Indoor unit cannot communicate
for more than 30 minutes after
the power on with remote
control.
3 .
Condition of error displayed
Same as above
4. Presumable cause
Improper setting
Surrounding environment
Defective remote control
communication circuit
Faulty indoor control or
power PCB
Faulty outdoor sub PCB
Note:
If any error is detected 30 minutes after displaying “
WAIT
” on the remote control, the display changes to
“INSPECT I/U”.
NO
NO
NO
NO
NO
Are more than
3 units of remote control
connected?
Does remote
control display
“Slave”?
YES
Do more than
one indoor units have the
same address?
Is it set to
a slave indoor unit.
SW5-1, 2?
Is there loose
or wrong connection at the termanal
of wiring between indoor and
outdoor units?
Is the
grounding wire connected
properly?
Is approx.
DC20V detected between -
on the outdoor unit terminal
block?
Is approx.
DC20V detected between -
on the indoor unit terminal
block?
YES
YES
YES
NO
NO
NO
YES
YES
YES
YES
Error code
Remote control:
LED Green Red
Indoor
Content