EasyManua.ls Logo

MobileView 7000 Series - Opening the G Sensor Menu; Alarm Menu; Opening the Alarm Menu

Default Icon
67 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MobileView 7000 Series User Manual 48
Z: This is defined as top to bottom on the device (+1G is normal)
Opening the G Sensor Menu
1. After opening the Status menu, select G Sensor to open the G sensor status.
2. The status displays, automatically updates, and cannot be changed.
G Sensor Menu
Alarm Menu
The alarm status menu dynamically displays the current state of digital and analog inputs monitored
by the device.
Digital: Monitored input is physically inactive/OFF (L) or active/ON (H)
Analog: Current voltage level of monitored input (range = 0VDC 30VDC)
CAUTION: Digital and analog inputs use a voltage range input. Each has expected operational
values and maximum allowed values as shown.
Digital Input
o Inactive/OFF State: 0VDC 5VDC
o No State Guarantee: 5VDC 6VDC
o Active/ON State: 6VDC 36VDC
o Max allowed voltage = 40VDC
Analog Input
o Voltage Range: 0VDC 36VDC
o Max allowed voltage = 40VDC
Opening the Alarm Menu
1. After opening the Status menu, select Alarm to open the alarm status.
2. Alarm status displays and cannot be changed. The status automatically updates.

Table of Contents