Quick Reference Guide
DF6 Frequency Inverter
02/02 AWB8230-1449GB
8
A021 1st fixed frequency 0.00 to 400 Hz 0.00
A022 2nd fixed frequency 0.00 to 400 Hz 0.00
A023 3rd fixed frequency 0.00 to 400 Hz 0.00
A024 4th fixed frequency 0.00 to 400 Hz 0.00
A025 5th fixed frequency 0.00 to 400 Hz 0.00
A026 6th fixed frequency 0.00 to 400 Hz 0.00
A027 7th fixed frequency 0.00 to 400 Hz 0.00
A028 8th fixed frequency 0.00 to 400 Hz 0.00
A029 9th fixed frequency 0.00 to 400 Hz 0.00
A030 10th fixed frequency 0.00 to 400 Hz 0.00
A031 11th fixed frequency 0.00 to 400 Hz 0.00
A032 12th fixed frequency 0.00 to 400 Hz 0.00
A033 13th fixed frequency 0.00 to 400 Hz 0.00
A034 14th fixed frequency 0.00 to 400 Hz 0.00
A035 15th fixed frequency 0.00 to 400 Hz 0.00
A038 Frequency in jog mode 0 to 9.99 Hz 1.00
A039 Motor stop in jog mode through • 00: Coasting
• 01: Deceleration ramp
• 02: DC braking
• 03: Without prior stop signal, motor coasts to halt
• 04: Without prior stop signal, stopping with
deceleration ramp
• 05: Without prior stop signal, stopping with
DC braking
00
A041 Voltage boost characteristics • 00: Manual
• 01: Automatic
00
A241 Boost characteristic
(second parameter set)
• 00: Manual
• 01: Automatic
00
A042 Percentage voltage increase with
manual boost
0.0 to 20 % 1.0
A242 Percentage voltage increase on
manual boost (second parameter set)
0.0 to 20 % 1.0
A043 Maximum boost at x % of the
base frequency
0.0 to 50 % 5.0
A243 Maximum boost at x % of the base
frequency (second parameter set)
0.0 to 50 % 5.0
A044 U/f characteristic • 00: Constant torque curve
• 01: Reduced torque curve
• 02: User-definable
00
A244 U/f characteristic (second parameter set) • 00: Constant torque curve
• 01: Reduced torque curve
• 02: User-definable
00
A045 Output voltage 20 to 100 % 100
A051 DC braking • 00: Inactive
• 01: Active
00
A052 DC braking starting frequency 0 to 60 Hz 0.5
A053 DC braking waiting time on deceleration 0 to 5 s 0.0
PNU Meaning Value range Def. Setpoint