02/02 AWB8230-1449GB
Standard form for user defined
parameter settings
9
A054 DC braking torque on deceleration 0 to 100 % 0
A055 DC braking duration on deceleration 0 to 60 s 0.0
A056 Behaviour on activation of the DB input 00: Starts on activation of the input,
ends after PNU A055
01: Runs as long as input is active
01
A057 DC braking torque on acceleration 0 to 100 % 0
A058 DC braking duration on acceleration 0 to 60 s 0.0
A059 DC braking frequency To DV6-340-55K: 0.5 to 15 kHz
From DF6-340-75K: 0.5 to 10 kHz
3.0
A061 Maximum operating frequency 0.00 to 400 Hz 0.0
A261 Maximum operating frequency
(second parameter set)
0.00 to 400 Hz 0.0
A062 Minimum operating frequency 0.00 to 400 Hz 0.0
A262 Minimum operating frequency
(second parameter set)
0.00 to 400 Hz 0.0
A063 1st frequency jump 0.00 to 400 Hz 0.0
A064 Jump width of the 1st frequency jump 0.00 to 10 Hz 0.5
A065 2nd frequency jump 0.00 to 400 Hz 0.0
A066 Jump width of the 2nd frequency jump 0.00 to 10 Hz 0.5
A067 3rd frequency jump 0.00 to 400 Hz 0.0
A068 Jump width of the 3rd frequency jump 0.00 to 10 Hz 0.5
A069 Acceleration pause waiting frequency 0.00 to 400 Hz 0.0
A070 Acceleration pause waiting duration 0 to 60 s 0.0
A071 PID control 00: Inactive
01: Active
00
A072 P component of the PID control 0.2 to 50 1.0
A073 I component of the PID control 0 to 3600 s 1.0
A074 D component of the PID control 0.0 to 100 s 0.0
A075 Setpoint factor of the PID control 0.01 to 99.99 1.00
A076 Input actual value signal for PID control 00: Input OI
01: Input O
00
A081 AVR function 00: Active
01: Inactive
02: Inactive during deceleration
02
A082 Motor voltage for AVR function 380, 400, 415, 440, 460, 480 400
A085 Energy-saving mode 00: Not active
01: Active
00
A086 Response time in energy-saving mode 0 to 100 s 50
A092 2. acceleration time 0.01 to 3600 s 15.0
A292 2nd acceleration time
(second parameter set)
0.01 to 3600 s 15.0
A093 2nd deceleration time 0.01 to 3600 s 15.0
A293 2nd deceleration time
(second parameter set)
0.01 to 3600 s 15.0
PNU Meaning Value range Def. Setpoint