Quick Reference Guide
DF6 Frequency Inverter
02/02 AWB8230-1449GB
10
A094 Changeover from 1st to 2nd time ramp • 00: Input 2CH
• 01: PNU A095 or A096
00
A294 Changeover from 1st to 2nd time ramp
(second parameter set)
• 00: Input 2CH
• 01: PNU A095 or A096
00
A095 Changeover frequency on changeover
from first to second acceleration time
0.00 to 400 Hz 0.00
A295 Changeover frequency on changeover
from first to second acceleration time
(second parameter set)
0.00 to 400 h 0.00
A096 Changeover frequency on changeover
from first to second deceleration time
0.00 to 400 Hz 0.00
A296 Changeover frequency on changeover
from first to second deceleration time
(second parameter set)
0.00 to 400 h 0.00
A097 Acceleration characteristic • 00: Linear
• 01: S curve
• 02: U curve
• 03: Inverted U curve
00
A098 Deceleration characteristic • 00: Linear
• 01: S curve
• 02: U curve
• 03: Inverted U curve
00
A101 Analog input OI starting frequency 0.00 to 400 Hz 0.00
A102 Analog input OI end frequency 0.00 to 400 h 0.00
A103 Analog input OI starting current 0 to 100 % 20
A104 Analog input OI end current 0 to 100 % 100
A105 Analog input OI condition for starting
frequency
00: Start at PNU A101
02: Start at 0 Hz
01
A111 Analog input O2 starting frequency –400 to 400 Hz 0.00
A112 Analog input O2 end frequency –400 to 400 Hz 0.00
A113 Analog input O2 starting voltage –100 to 100 % –100
A114 Analog input O2 end voltage –100 to 100 % 100
A131 Curvature of acceleration characteristic 01 to 10 02
A132 Curvature of deceleration characteristic 01 to 10 02
PNU Meaning Value range Def. Setpoint