13
Electronic mounting and installation drawings are included in the CD provided.
In most cases the factory will install the monitor on Unistrut
®
brackets that are welded to the main
transformer tank. Calisto/Calisto 2 is generally installed at eye level and two additional ½ inch valves
are welded directly to the main tank near the monitor for the oil supply and return.
In most cases the top oil fill valve and the main drain valve are located on the same side of the main
tank. It is best to install the monitor near the bottom drain valve. Of course this location will vary as
needed based on the oil line requirements discussed later in this section.
Typically Unistrut
®
brackets are used to make a base for mounting the Calisto/Calisto 2. The
mounting structure can be designed to clamp on to various components of the transformer tank, on
the main control cabinet, on a post installed in the ground or on a concrete base. A Morgan Schaffer
Calisto Mounting Stand is available as an optional accessory. Contact Morgan Schaffer for more
information.
A complete Installation Manual is included with the Morgan Schaffer Calisto Mounting Stand
accessories. Refer to this manual when mounting a Calisto/Calisto 2 on the stand.