22
29
Low DC cut-off voltage
1KVA default setting: 10.5V
2K/3KVA default setting: 21.0V
4K/5KVA default setting: 42.0V
If self-defined is selected in program 5, this program can
be set up. Setting range is from 10.0V to 12.0V for 1K
model, 20.0V to 24.0V for 2K/3K model and 40.0V to 48.0V
for 4K/5K model. Increment of each click is 0.1V. Low DC
cut-off voltage will be fixed to setting value no matter what
percentage of load is connected.
31
Solar power balance:
When enabled, solar input
power will be automatically
adjusted according to
connected load power.
(Only available for
4KVA/5KVA model)
Solar power balance
enable (Default):
If selected, solar input power will
be automatically adjusted
according to the following formula:
Max. input solar power = Max.
battery charging power +
Connected load power.
Solar power balance
disable:
If selected, the solar input power
will be the same to max. battery
charging power no matter how
much loads are connected. The
max. battery charging power will
be based on the setting current in
program 02.
(Max. solar power = Max. battery
charging power)