When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bulk charging voltage
(C.V voltage)
1KVA default setting: 14.1V
2K/3KVA default setting: 28.2V
4K/5KVA default setting: 56.4V
If self-defined is selected in program 5, this program can
be set up. Setting range is from 12.0V to 14.6V for 1K
model, 24.0V to 29.2V for 2K/3K model and 48.0V to 58.4V
for 4K/5K model. Increment of each click is 0.1V.
Floating charging voltage
1KVA default setting: 13.5V
2K/3KVA default setting: 27.0V
4K/5KVA default setting: 54.0V
If self-defined is selected in program 5, this program can
be set up. Setting range is from 12.0V to 14.6V for 1K
model, 24.0V to 29.2V for 2K/3K model and 48.0V to 58.4V
for 4K/5K model. Increment of each click is 0.1V.