EasyManua.ls Logo

MQ Power DCA25SSIU4F - MAINTENANCE; Table 14. Inspection;Maintenance

MQ Power DCA25SSIU4F
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PAGE 34 — DCA25SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #4 (01/17/18)
Table 14. Inspection/Maintenance
10 Hrs
DAILY
250 Hrs
500 Hrs
or Every
12 Months
3000 Hrs
or Every
36 Months
OTHER
Engine
Check Engine Oil and Coolant Levels X
Check Fuel Filter/Water Separator Bowl X
Check Air Cleaner X
Check Air Cleaner Element X
Check for Leaks/Hoses/Clamps X
Check for Loosening of Parts X
Change Engine Oil and Oil Filter *
1
X
Clean Unit, Inside and Outside X
Replace Fuel Filter Elements X
Check Engine Mounts X
Service Battery X
Check Air Intake Hoses X
Check Fan Belt Condition X
Check Automatic Belt Tensioner X
Check Electrical Ground Connection X
Clean Radiator, Check Cooling System X
Coolant Solution Analysis, Add SCA's As Required X
Pressure Test Cooling System X
Check Engine Speed X
Test Thermostats X
Test Glow Plugs X
Flush and Refill Cooling System 2 yrs. or 2000 hrs.
Clean Inside of Fuel Tank 1000 hrs.
Replace Air Cleaner Elements *
2
As Required
Generator
Measure Insulation Resistance Over 3M ohms X
Check Rotor Rear Support Bearing X
*
1
During initial operation of a new engine, change oil and filter between a minimum of 100 hrs. and a maximum of 250 hrs. Service interval depends
on type of oil.
*
2
Replace primary air filter element when restriction indicator shows a vacuum of 625 mm (25 in. H
2
0).