9 Visualization
Maschinenfabrik Reinhausen GmbH 2020 2754453918/14 EN ETOS
®
TD
Events
No.
Event Time
8
Limit value I>>
17.03.2020
10:56:59/669
12
Limit value S>>
16
Limit value P>>
18
Limit value Q<<
1001
Ambient temperature invalid
1002
Ambient temperature
17.03.2020
10:56:59/669
17.03.2020
10:56:59/669
17.03.2020
10:56:59/669
17.03.2020
10:56:59/669
17.03.2020
3
12
38
Log
Confirm
EN CHANGE REBOOTadmin 23.03.2020 08:08
Figure208: Overview of events currently active
Acknowledging events
Acknowledgeable events must be acknowledged in the event overview so
that they are no longer displayed. All other events are automatically removed
once the cause is remedied (e.g. limit value no longer infringed).
To acknowledge the events, proceed as follows:
► To acknowledge the events, highlight the desired events in the column
then press the Acknowledge button.
ð The events are acknowledged.
9.33.2 Configuring events
The events have the following properties:
Property Description
Event name Brief name of event. If you delete all of the text, the stan-
dard text is displayed.
Event description Description of event. If you delete all of the text, the stan-
dard text is displayed.
Event troubleshooting Instructions for troubleshooting the cause of an event. If
you delete all of the text, the standard text is displayed.
Category ▪ Error (red)
▪ Warning (yellow)
▪ Info (gray)
This setting affects the color of the Alarm LED and the
event symbol in the primary navigation.
Report If you activate this option, the event is shown on the dis-
play and, if configured accordingly, issued via an output
and the control system protocol.