12 Event messages
Maschinenfabrik Reinhausen GmbH 2020 3134453918/14 EN ETOS
®
TD
12 Event messages
No. Name Description Remedy
1 Limit value U< Value has fallen below the limit
value for undervoltage U<.
Check the current operating conditions of the
transformer and the set U< parameters.
2 Limit value U<< Value has fallen below the limit
value for undervoltage U<<.
Check the current operating conditions of the
transformer and the set U<< parameters.
3 Limit value U> The limit value for overvoltage U>
has been exceeded.
Check the current operating conditions of the
transformer and the set U> parameters.
4 Limit value U>> The limit value for overvoltage
U>> has been exceeded.
Check the current operating conditions of the
transformer and the set U>> parameters.
5 Limit value I< Value has fallen below the limit
value for undercurrent I<.
Check the current operating conditions of the
transformer and the set I< parameters.
6 Limit value I<< Value has fallen below the limit
value for undercurrent I<<.
Check the current operating conditions of the
transformer and the set I<< parameters.
7 Limit value I> The limit value for overcurrent I>
has been exceeded.
Check the current operating conditions of the
transformer and the set I> parameters.
8 Limit value I>> The limit value for overcurrent I>>
has been exceeded.
Check the current operating conditions of the
transformer and the set I>> parameters.
9 Limit value S< Value has fallen below the limit
value for apparent power S<.
Check the current operating conditions of the
transformer and the set S< parameters.
10 Limit value S<< Value has fallen below the limit
value for apparent power S<<.
Check the current operating conditions of the
transformer and the set S<< parameters.
11 Limit value S> The limit value for apparent
power S> has been exceeded.
Check the current operating conditions of the
transformer and the set S> parameters.
12 Limit value S>> The limit value for apparent
power S>> has been exceeded.
Check the current operating conditions of the
transformer and the set S>> parameters.
13 Limit value P< Value has fallen below the limit
value for active power P<.
Check the current operating conditions of the
transformer and the set P< parameters.
14 Limit value P<< Value has fallen below the limit
value for active power P<<.
Check the current operating conditions of the
transformer and the set P<< parameters.
15 Limit value P> The limit value for active power
P> has been exceeded.
Check the current operating conditions of the
transformer and the set P> parameters.
16 Limit value P>> The limit value for active power
P>> has been exceeded.
Check the current operating conditions of the
transformer and the set P>> parameters.
17 Limit value Q< Value has fallen below the limit
value for reactive power Q<.
Check the current operating conditions of the
transformer and the set Q< parameters.
18 Limit value Q<< Value has fallen below the limit
value for reactive power Q<<.
Check the current operating conditions of the
transformer and the set Q<< parameters.
19 Limit value Q> The limit value for reactive power
Q> has been exceeded.
Check the current operating conditions of the
transformer and the set Q> parameters.
20 Limit value Q>> The limit value for reactive power
Q>> has been exceeded.
Check the current operating conditions of the
transformer and the set Q>> parameters.
21 Limit value cos φ < Value has fallen below the limit
value for power factor cos f<.
Check the current operating conditions of the
transformer and the set parameters cos f<.