9 Visualization
Maschinenfabrik Reinhausen GmbH 202080 4453918/14 ENETOS
®
TD
Assign IP addresses to both web-based visualization and SCADA (optional)
in different subnets. Otherwise you will not be able to establish a connec-
tion.
Subnet mask ETH 1/ETH 2.2
You can use this parameter to set the subnet mask.
Be sure to enter a valid network mask that is not 0.0.0.0, otherwise it will not
be possible to connect to the device.
Gateway address ETH 1/ETH 2.2
You can use this parameter to set the gateway's IP address.
If you set the value to 0.0.0.0, no gateway is used.
Visualization release
You can use this parameter to set the interfaces via which you can access
the visualization:
▪ Only ETH2.x
▪ ETH1 and ETH2.x
You can only set this parameter if the device is equipped with the optional
control system connection via Ethernet (TCP/IP) and the optional interface
for visualization.
SSL/TLS encryption
You can use this parameter to set whether the process for accessing the vi-
sualization should be carried out over an SSL/TLS-encrypted connection.