8.25.3 LOP – Test procedures
Preconditions
☑ Engine is stopped and starting disabled.
Preparatory steps
1. Connect battery in accordance with battery
manufacturer's instructions.
2. Switch master power switch to ON.
3. Switch on engine management system
ECS-5.
Result: • LOCAL OPERATION button (1) is illuminat-
ed brightly (local control mode is active).
• COUPLING NEUTRAL button (2) is illumi-
nated brightly (gearbox disengaged).
Switching between local and re-
mote control mode
1. Press LOCAL OPERATION illuminated push-
button (1).
Result: • LOCAL OPERATION button (1) flashes: Set-
ting does not correspond with feedback
signal from ECU and GCU.
• LOCAL OPERATION button (1) is illuminat-
ed at basic brightness: Remote control
mode is active.
2. Press LOCAL OPERATION illuminated push-
button (1) again.
Result: LOCAL OPERATION button (1) is illuminated
brightly (local control mode is active).
MW15409/04E 2015-08 | Task Description | 153