836 – AL Nominal Speed Setting Fail
Yellow alarm; warning
Cause Corrective action
Active analog speed setting faulty. u Check wiring (CAN MD).
851 – AL Extern Start and HD too high
Entered in fault memory only
Cause Corrective action
An external start is pending and
high pressure is too high.
u Contact Service.
852 – AL Max. Blankshot Time Expired
Yellow alarm; warning
Cause Corrective action
High pressure could not be
released in the max. blankshot
time.
u Contact Service.
947 – AL Wrong LSI Channel Config
Yellow alarm; warning
Cause Corrective action
Data fault on allocating LSI
channels.
u Contact Service.
973 – AL Checksum IIG
Yellow alarm; warning
Cause Corrective action
Checksum calculation or word
limit check for one of the injectors
is not correct.
u Contact Service.
1130 – AL Short Circuit Analog Output 1
Yellow alarm; warning
Cause Corrective action
The value output at analog output
1 deviates excessively from the
value read back.
u Check wiring.