Fault
code no. Full designation Meaning Action
Setting parame-
ter no.
308 AL Timing Cylinder A8 Time-of-flight measuring fault
injector cylinder A8 Time-of-
flight value measured ex-
tremely small or large (alarm
configuration parameter, see
PR 2.8008.100 for explana-
tion).
Replace plug-in
pump if this occurs
frequently.
1.8004.507
309 AL Timing Cylinder A9 Time-of-flight measuring fault
injector cylinder A9 Time-of-
flight value measured ex-
tremely small or large (alarm
configuration parameter, see
PR 2.8008.100 for explana-
tion).
Replace plug-in
pump if this occurs
frequently.
1.8004.508
310 AL Timing Cylinder A10 Time-of-flight measuring fault
injector cylinder A10: Time-
of-flight value measured ex-
tremely small or large (alarm
configuration parameter, see
PR 2.8008.100 for explana-
tion).
Replace plug-in
pump if this occurs
frequently.
1.8004.509
311 AL Timing Cylinder B1 Time-of-flight measuring fault
injector cylinder B1: Time-of-
flight value measured ex-
tremely small or large (alarm
configuration parameter, see
PR 2.8008.100 for explana-
tion).
Replace plug-in
pump if this occurs
frequently.
1.8004.510
312 AL Timing Cylinder B2 Time-of-flight measuring fault
injector cylinder B2: Time-of-
flight value measured ex-
tremely small or large (alarm
configuration parameter, see
PR 2.8008.100 for explana-
tion).
Replace plug-in
pump if this occurs
frequently.
1.8004.511
313 AL Timing Cylinder B3 Time-of-flight measuring fault
injector cylinder B3: Time-of-
flight value measured ex-
tremely small or large (alarm
configuration parameter, see
PR 2.8008.100 for explana-
tion).
Replace plug-in
pump if this occurs
frequently.
18004.512
314 AL Timing Cylinder B4 Time-of-flight measuring fault
injector cylinder B4: Time-of-
flight value measured ex-
tremely small or large (alarm
configuration parameter, see
PR 2.8008.100 for explana-
tion).
Replace plug-in
pump if this occurs
frequently.
1.8004.513
54 | Troubleshooting | MS15018/03E 2016-02
TIM-ID: 0000008508 - 003