Setpoint
Information
Max Time Lockout Safety Sec to Window to Safety
Adjust Time Allowed Delay Down Display Auth Level Type of Ignore Extend Time High Low Night MIN VFD MAX VFD MAX VFD BMS
# Name Value Low High Value (SEC) (SEC) Hours Time(Min) Type To Display Setpoint Safety Sfty Time(Sec) Ext.(Sec) Zone Zone Setback Opening Opening Adjustment Writable
1 ColdTankTarg 44 44 65 0.5 0 0 TEMP View Only Target ----- ----- ----- 1.0 1.0 0 ----- ----- ----- No
2 HotTankTarg 115 80 140 0.5 0 0 TEMP View Only Target ----- ----- ----- 0.5 1 0 ----- ----- ----- No
9 SUPERHTTRG 17 10 20 0.5 4 10 2 5 TEMP View Only Alarm 0 0 0 ----- ----- ----- ----- ----- ----- No
10 SPRHTZONE+/- 1.0 1 4 0.1 0 0 TEMP View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
11 EXV LOAD ADJ 0.3 0.1 1 0.1 0 0 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
12 EXV FINE ADJ 0.1 0.1 2 0.1 0 0 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
13 EXV COURSE 0.5 0.2 5 0.1 4 5 HUMD or % View Only Time ----- ----- ----- ----- ----- ----- ----- ----- ----- No
15 EXV MIN% 10 5 50 1 0 0 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
16 EXV MAX% 100 25 100 1 0 0 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
17 LO SUPERHEAT 3 3 6 1 180 240 2 10 TEMP View Only Alarm 0 300 60 ----- ----- ----- ----- ----- ----- No
18 LOSUCTPSIDLY 2 2 30 1 0 0 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
19 EXV DELAY 60 30 120 1 0 0 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
20 EXV STRT TME 5 1 10 1 5 10 SECONDS View Only Time ----- ----- ----- ----- ----- ----- ----- ----- ----- No
22 LOW AMBIENT -22 -40 70 1 0 0 TEMP View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
23 POWERUP DLAY 15 10 120 5 0 0 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
25 STEP SENSIT 1 1 10 1 0 0 DIGITAL/SW View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
26 STEP DELAY 180 60 600 10 120 120 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
27 MAX ROC- -0.8 -2 -0.6 0.1 0 0 TEMP View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
28 MAX ROC+ 0.8 0.6 2 0.1 0 0 TEMP View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
29 ROC INTERVAL 60 30 60 5 0 0 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
30 MAX LOAD% 77 50 100 1 0 0 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
31 MIN LOAD% 40 20 50 1 0 0 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
32 MAX ADJUST % 6 1 20 1 1 1 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
33 MIN ADJUST % 2 1 5 1 0 0 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
34 LOAD SENSIT 1 1 10 1 0 0 DIGITAL/SW View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
48 CND DELAY 10 5 120 1 0 0 SECONDS View Only Delay ----- ----- ----- ----- ----- ----- 1 1 0 No
49 CdFanStrt% 20 20 100 5 1 1 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
50 CND TARG PSI 330 225 450 5 0 0 PSI GAGE View Only Target ----- ----- ----- 7.5 7.5 0 ----- ----- ----- No
51 CND FAN DIV 7 1 25 1 1 1 DIGITAL/SW View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
52 CND MIN SPD 10 15 50 1 1 1 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
53 CND ROC- -8 -20 -1 1 0 0 PSI GAGE View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
54 CND FAN MULT 1 1 25 1 0 0 DIGITAL/SW View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
55 CND MIN ADJ 1 0.5 10 0.5 0 0 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
56 CMP ADJ DELY 2 1 5 1 30 30 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
59 A-CYC OFF-ON 60 30 600 10 0 0 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
61 CMP OFF RPMs 1100 0 0 0 0 0 RPM View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
62 CMP SpinDown 60s 15 0 0 0 0 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
63 A-CYC ON-ON 120 60 1500 10 0 0 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
64 COMP MIN RUN 2 1 10 1 0 0 MINUTES View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
75 HI AMPS % 115 20 125 1 5 5 2 5 HUMD or % View Only Lockout 0 0 0 ----- ----- ----- ----- ----- ----- No
76 LOampNoSTART 5 5 40 1 40 40 2 10 HUMD or % View Only Lockout 0 0 0 ----- ----- ----- ----- ----- ----- No
77 LOW SUCTION 65.0 80 180 1 120 300 2 10 PSI GAGE View Only Lockout 0 300 120 ----- ----- ----- ----- ----- ----- No
78 LO SUCT UNLD 3 1 5 1 0 0 2 10 PSI GAGE View Only Alarm 0 0 0 ----- ----- ----- ----- ----- ----- No
79 LO SUCT RELD 5 2 8 1 0 0 PSI GAGE View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
80 UNSAFE SUCT 80 0 10 1 3 10 0 0 PSI GAGE View Only Lockout 0 120 6 ----- ----- ----- ----- ----- ----- No
81 HI DISC PSI 575 300 620 10 2 2 2 10 PSI GAGE View Only Lockout 0 0 0 ----- ----- ----- ----- ----- ----- No
Continued on Next Page--->
APPENDIX F - MHRC CONFIGURATION - FACTORY SETPOINT PRESETS