Setpoint
Information
Max Time Lockout Safety Sec to Window to Safety
Adjust Time Allowed Delay Down Display Auth Level Type of Ignore Extend Time High Low Night MIN VFD MAX VFD MAX VFD BMS
# Name Value Low High Value (SEC) (SEC) Hours Time(Min) Type To Display Setpoint Safety Sfty Time(Sec) Ext.(Sec) Zone Zone Setback Opening Opening Adjustment Writable
82 HI DISC UNLD 35 10 50 1 0 0 PSI GAGE View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
83 HI DISC RELD 50 20 80 1 0 0 PSI GAGE View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
87 HI DISCH TMP 230 180 230 1 2 5 2 10 TEMP View Only Lockout 0 0 0 ----- ----- ----- ----- ----- ----- No
88 DIS TMP UNLD 5 3 10 1 0 0 TEMP View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
89 DIS TMP RELD 10 5 15 1 0 0 TEMP View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
91 LOW DIF PSI 15 80 180 1 50 60 2 10 PSI GAGE View Only Lockout 30 0 0 ----- ----- ----- ----- ----- ----- No
92 UnsafeDifPsi 5.0 40 80 1 40 90 0 0 PSI GAGE View Only Lockout 15 0 0 ----- ----- ----- ----- ----- ----- No
101 SAFETY HOLD 120 60 600 10 2 2 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
105 NO FLOW 120 5 120 1 0 0 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
108 PMP OFF DLAY 120 30 300 10 0 0 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
111 FREEZE 35 33 50 0.5 3 3 0 10 TEMP View Only Lockout 0 0 0 ----- ----- ----- ----- ----- ----- No
139 HI PSI SW 0 2s 1 0 0 0 PSI GAGE View Only Lockout 0 ----- ----- ----- ----- ----- ----- ----- ----- No
151 Unloaded Off 2 1 3 0.5 1 1 TEMP View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
153 SftyUnld Dly 5.0 2 30 1 0 0 SECONDS View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
154 SftyUnld Adj 5 2 10 1 0 0 HUMD or % View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
157 HP LoSuctAdj 80 5 50 1 0 0 PSI GAGE View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
158 DEF START TMP 5.0 0 50 1 0 0 TEMP View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
159 DEF START DEL 30 0 300 1 0 0 MINUTES View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
161 DEF STOP TMP 55 30 180 1 0 0 TEMP View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
162 DEFSTOPDelay 5.0 0 60 1 0 0 MINUTES View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
163 CND HP OFSET 230 80 150 0.5 0 0 TEMP View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
164 SwModeDelay 45s 0 0 0 0 0 SEC View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
171 FLA COMP#1 35 8 40 1 0 0 AMPS/CT View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
212 CmpVFDFault 1 0 0 2 2 0 PSI GAGE View Only Setpoint ----- ----- ----- ----- ----- ----- ----- ----- ----- No
APPENDIX F - MHRC CONFIGURATION - FACTORY SETPOINT PRESETS