M120
8.3Technicaldata
Processair
(1)
Free-blowingair50Hz(m³/h)
180
Free-blowingair60Hz(m³/h)
210
Ratedairow(m³/h)
120
Availablestaticpressure50Hz(Pa)
200
Availablestaticpressure60Hz(Pa)
360
Fanmotorpower(kW)
0,030
Reactivationair
(1)
Ratedairow(m³/h)
35
Availablestaticpressure(Pa)
100
Fanmotorpower(kW)
(2)
-
Totalpower,voltageandcurrent
TotalPower(kW)
1,3
Voltage(V)
115220230
Ratedcurrent50Hz(A)
10,96,3
5,7
Ratedcurrent60Hz(A)
11,66,66,0
Reactivationairheater
Heaterpower(kW)
1,2
Temperatureincreaseacrossheater100
Miscellaneousdata
Drivemotorpower(W)
18
Maxnoiselevelunducted(dBa)
48
IECprotectiveclass
IP44
Impacttestacc.toIEC-60068-2-27
(3)
20Gfor25ms
Rotortype
HPS
Weight(kg)
26
Environmentalconditions
Operatingtemperature(°C)
-40...+40
Maximuminstallationaltitude,abovesealevel(m)
2000
Transportandstoragetemperature(°C)
-40...+70
(1)Figuresquotedarebasedonfaninlettemperatureof20°C,andanairdensityof1,2kg/m
3
(2)Commonmotorforprocessandreactivationfans
(3)Resistancecheckedin3directions
Table8.2Technicaldata
190TGB-1008-H1402Technicalspecication20