DehumidierML420-MLT1400
ParameterDescriptionPossibleparameterselectionDefaultsetting
01Proportionalband1-15%RH5
02Integrationtime0-99seconds0(=off)
03Differentialaction,percentage0-100%RH0(=off)
04Cycletime0-999seconds20
05Correctionofthehumiditysensors’svalue-15-+15%RHNosettings
10Offset,relay-20-20%RH10
11Differential,relay-21-5%RH1
20Minimumsetpoint0-100%RH0
21Maximumsetpoint0-100%RH100
40Delayinregainingsupplyafterapowercut0-99min.0
41Forcedsolid-stateoutputwheresensorfault0=No;1=100%output0
42Forcedrelay-2outputwheresensorfault0=No;1=Yes0
Table1.2Operatorpanelsystemparameters–VariDry
46Options190TGB-1035-H1604