9. TROUBLESHOOTING
WARNING
Moving parts, disconnect power before servicing.
WARNING
High voltage, disconnect power before servicing.
SYMPTOM
POSSIBLE CAUSES
CORRECTIVE ACTION
Fan not operating
Fan control set above room temperature
Blown Fuse or open circuit breaker
Propeller blade contacting fan housing
Fan control defecting
Motor defective
Set a lower temperature
Replace fuse or reset breaker
Realign motor in fan housing
Repair or replace control
Repair or replace motor
Fan operating -
insufficient airflow
Damper door jammed
Guard dirty/clogged
Clean damper door & fan housing
Clean guard
Excessive noise
Propeller blade contacting fan housing
Sand fan housing to remove high spot
Excessive vibration
Motor loose on mount
Propeller damaged
Motor or propeller shaft bent
Tighten fasteners
Replace propeller
Repair or replace motor or propeller shaft
Fan never turns off
Override thermostat set incorrectly
Control set for continuous operation
Set to the correct temperature
Set control correctly
It is normal that the damper does not open completely. No corrective actions are needed.